Methane Gas Detector

Bautech GD-KNG

It is a device designed to alert in case of methane gas leaks.

• Compact size and lightweight;

• Multiple installation methods at user's choice;

• High-performance sensor;

• Improved version for sensor defect detection and error compensation algorithm;

• Electrovalve status detection function;

• Easy-to-replace power cables.

Model:
GD-KNG
Detectable Gas:
CH₄ / Methane Gas
Operating Voltage:
AC 220 V±15%
Power Consumption:
Static Power Consumption 0.3W
Static Power Consumption 0.5W
Operating Temperature:
-10℃~55℃
Ambient Environment:
Temperature: 0°C - +40°C
Humidity: <93%RH without condensation
Ambient Pressure:
86kPa~106kPa
Response Time:
≤30s self-recovery
Detection Range:
0~20%LEL
Alarm Value:
10% LEL
Alarm Sound:
>85dB@1m
Alarm Methods:
audio and visual
Features:
optional solenoid valve or relay output
Weight:
250g, including adapter
Dimensions:
85.6mm × 85mm × 40.5mm
Sensor Lifespan:
>5 years
Sensor:
semiconductor
Protection Grade:
IP30
Accuracy:
Conforming to EN50291/2018

Technical Details

Download the PDF file with all technical details here.